Formula
Adjusted ampacity is the Table 310.16 value in the insulation column, times the Table 310.15(B)(1)(1) ambient factor for that same column, times the Table 310.15(C)(1) bundling factor. Usable ampacity is the lesser of that adjusted value and the Table 310.16 value in the termination column. NEC 110.14(C)(1)(a) uses the 60 °C column for equipment rated 100 A or less, and for 14 AWG through 1 AWG, unless the terminations are listed and marked otherwise. The 75 °C choice on this page is for equipment that is marked for it.
adjusted = Table 310.16 × ambient × bundling
usable = min(adjusted, termination column)
NEC 240.4(D) caps the overcurrent device at 15 A for 14 AWG copper, 20 A for 12 AWG copper, 30 A for 10 AWG copper, 15 A for 12 AWG aluminum, and 25 A for 10 AWG aluminum. Where 240.4(B) allows the next standard size in 240.6(A), this page uses it only through 800 A, and not when you mark a multioutlet branch circuit for cord-and-plug loads. A continuous load uses 125 percent under 210.19(A)(1) and 210.20(A). NM-B starts in the 90 °C column and NEC 334.80 takes the final ampacity from the 60 °C column. Motor circuits are Article 430. Air-conditioning nameplate protection is Article 440. Dwelling service and feeder sizing under 310.12 is a different rule. None of those are calculated here.
Worked examples
12 AWG copper, THHN, 75 °C terminations, 30 °C, 3 conductors. 75 °C column 25 A. Maximum breaker 20 A under 240.4(D). 6 AWG copper, THHN, 75 °C terminations. The 90 °C value is 75 A. Terminations limit it to 65 A. Next standard size is 70 A, only where 240.4(B) allows it.
4 AWG aluminum, 75 °C. 65 A. 10 AWG copper THHN, 40 °C, 5 conductors, 75 °C terminations. 40 × 0.91 × 0.80 = 29.1 A, and the 240.4(D) cap is 30 A. 24 A continuous. 30 A breaker, 10 AWG copper at 75 °C. 32 A continuous on NM-B. 40 A breaker, 8 AWG copper, 60 °C column 40 A.
Reference
| Size | Cu 60 | Cu 75 | Cu 90 | Al 60 | Al 75 | Al 90 |
|---|---|---|---|---|---|---|
| 14 | 15 | 20 | 25 | — | — | — |
| 12 | 20 | 25 | 30 | 15 | 20 | 25 |
| 10 | 30 | 35 | 40 | 25 | 30 | 35 |
| 8 | 40 | 50 | 55 | 35 | 40 | 45 |
| 6 | 55 | 65 | 75 | 40 | 50 | 55 |
| 4 | 70 | 85 | 95 | 55 | 65 | 75 |
| 3 | 85 | 100 | 115 | 65 | 75 | 85 |
| 2 | 95 | 115 | 130 | 75 | 90 | 100 |
| 1 | 110 | 130 | 145 | 85 | 100 | 115 |
| 1/0 | 125 | 150 | 170 | 100 | 120 | 135 |
| 2/0 | 145 | 175 | 195 | 115 | 135 | 150 |
| 3/0 | 165 | 200 | 225 | 130 | 155 | 175 |
| 4/0 | 195 | 230 | 260 | 150 | 180 | 205 |
Questions
How many amps can 12 gauge wire carry?
NEC 2023 Table 310.16 lists 12 AWG copper at 20 A, 25 A, and 30 A in the 60, 75, and 90 °C columns. With 75 °C terminations the usable figure is 25 A. NEC 240.4(D) still limits the breaker to 20 A.
What size breaker for 10 gauge wire?
10 AWG copper is 30, 35, and 40 A in the three columns. NEC 240.4(D) limits the breaker to 30 A. Aluminum 10 AWG is limited to 25 A.
What size wire for a 50 amp breaker?
At 75 °C terminations, 30 °C, and three current-carrying conductors, 8 AWG copper is 50 A in the 75 °C column and 6 AWG copper is 65 A. Eight AWG meets 50 A before any extra derating. A continuous load is figured at 125 percent. Check the run with the inspector or a licensed electrician.
What is wire derating?
Ambient temperature uses Table 310.15(B)(1)(1). More than three current-carrying conductors use Table 310.15(C)(1). Both multiply the insulation column. The termination column then caps the result.
Why is 12 AWG on a 20 A breaker if the table says 25 A?
The 75 °C column is 25 A. NEC 240.4(D) is a separate small-conductor limit: 15 A for 14 AWG copper, 20 A for 12 AWG copper, and 30 A for 10 AWG copper.
What is a continuous load?
A load expected to run for three hours or more. NEC 210.20(A) and 210.19(A)(1) size the breaker and the conductor at 125 percent of that load. This page does not size a motor or an air conditioner.
Does NM-B use the 60 °C column?
NEC 334.80 takes the final ampacity of NM-B from the 60 °C column. The conductors are 90 °C, so correction starts in the 90 °C column and the 60 °C column caps it. Eight AWG copper is 40 A in that 60 °C column.
Sources
- NEC 2023 Table 310.16, copper and aluminum, 60 °C, 75 °C, and 90 °C columns, checked against a full-table printing that reports zero mismatches with the NFPA table. The 75 °C column is the same module the wire-size page uses.
- NFPA, “Using the National Electrical Code Ampacity Charts,” 2023 edition fact sheet: Table 310.15(B)(1)(1) ambient factors and Table 310.15(C)(1) adjustment factors.
- NEC 240.4(D), 240.4(B), 240.6(A), 110.14(C), 210.19(A)(1), 210.20(A), and 334.80, as applied on this page. Articles 430, 440, and the 310.12 dwelling rule are named only to say they are not used.