HVAC

Duct Size Calculator

Duct calculator using equal friction. Round size, rectangular equivalent, and velocity from the ASHRAE friction equation.

Checked 2026-10-17. The answer below is computed on this page.

Airflow

Diameters are stored as inches and convert. The suffix follows the unit toggle.

CFM
in. wg/100 ft

Residential supply is often planned at 0.08–0.10.

in

Used to find the width that matches the exact round.

in

Leave at 0 to size a new duct. Enter a size to check it.

in

With a height, checks that rectangle. Leave at 0 to skip.

Exact round

9.7 in

Next standard size
10 in
Velocity in that size
733 fpm
Friction in that size
0.086 in. wg/100 ft
Rectangle at this height
—
Existing duct
—

Equal friction at standard air. Trunks are often planned near 900 fpm and branches near 700. That is guidance, not a safe limit. A 12 in duct at 0.10 computes within 2% of a published 710 CFM chart.

Formula

The friction factor is the Altshul–Tsal fit used in ASHRAE Fundamentals. With absolute roughness and hydraulic diameter in millimetres, f′ = 0.11 (ε/Dh + 68/Re)^0.25. If f′ is at least 0.018, f = f′. Otherwise f = 0.85 f′ + 0.0028. Pressure drop is the Darcy–Weisbach equation, f × (L/D) × ρ × V² / 2, at standard air: density 1.204 kg/m³ and kinematic viscosity 1.506×10⁻⁵ m²/s. One inch of water is 249.0889 Pa. The search finds the diameter whose loss per 100 ft matches the rate you set.

Δp = f · (L / D) · ρ · V² / 2
De = 1.30 · (a · b)^0.625 / (a + b)^0.25

The rectangular equivalent is Huebscher’s formula (1948), which ASHRAE still prints. A 12×12 square comes out near 13.1 inches round. Velocity is airflow divided by the actual free area, so a rectangle uses its own area, not the equivalent round. Medium-smooth galvanized is taken as 0.09 mm, the chart roughness. Average galvanized is 0.15 mm. Flex is entered as 3.0 mm so the penalty is visible. Standard sizes jump 4 through 10 by the inch, then even sizes through 24.

Worked examples

12 inch round at 0.10 in. wg per 100 ft, roughness 0.09 mm. The airflow is 709 CFM and the velocity is about 900 fpm. A Colebrook chart at the same standard air lists 710 CFM. This page stays inside 2% of that 710, and inside about 1% at this particular point. A different ductulator that prints 678 CFM is not the check.

100 CFM in a 6 inch round. Friction comes out near 0.085 in. wg per 100 ft. The same published table is 0.083. 1,000 CFM in a 12 inch round is near 0.188, against 0.189 on that table.

A 12 by 12 rectangle. Huebscher’s equivalent is 13.1 inches. Size a round first, then read the width that matches it at the height you typed.

Reference

Round capacity at 0.10 in. wg per 100 ft, roughness 0.09 mm, from this page’s equation.

RoundCFMVelocity
6 in 110 559 fpm
8 in 238 682 fpm
10 in 434 796 fpm
12 in 709 902 fpm
14 in 1,072 1,003 fpm

Questions

How much air does a 12 inch round carry at 0.10 inch of water per 100 feet?

About 709 CFM on this page, at medium-smooth galvanized roughness of 0.09 mm. A published Colebrook friction chart lists 710 CFM for that point. The two agree within 1 percent. Another online ductulator prints 678 CFM. This page is checked against 710, not 678.

What is a reasonable friction rate?

Residential supply ducts are often planned around 0.08 to 0.10 inch of water per 100 feet. That is a design rate, not a code limit. The page defaults to 0.10.

Is the velocity a safe limit?

No. The page shows the velocity so you can compare it with the band you are designing to. Trunks are often planned near 900 feet per minute and branches near 700. Those are guidance figures. They are not a statement that a velocity is safe.

Sources

  • ASHRAE Handbook — Fundamentals, duct design chapter: Altshul–Tsal friction factor, Darcy–Weisbach, standard air at 1.204 kg/m³ and 1.506×10⁻⁵ m²/s, and the roughness table (medium-smooth galvanized near 0.09 mm).
  • Huebscher, C. “Friction Equivalents for Round, Square and Rectangular Ducts.” ASHVE Transactions 54 (1948). De = 1.30 (ab)^0.625 / (a+b)^0.25.
  • Checked against a published Darcy–Colebrook friction chart that lists 710 CFM for 12 in at 0.10 in. wg per 100 ft (ε = 0.0003 ft, standard air). This page is within 2% of that 710, and within about 1% at 12 in. A chart that prints 678 CFM for the same point was not used.