Plumbing

Pipe Flow Calculator

Water velocity, the inside diameter for a velocity limit, and Reynolds number. Hazen–Williams head loss is the friction-loss formula. Not fixture-unit code sizing.

Checked 2026-11-10. The answer below is computed on this page.

Pipe

in
GPM
ft/s

Copper Tube Handbook: 8 ft/s cold, 5 ft/s hot up to about 140°F, 2–3 ft/s if the water is routinely hotter. Copper only. Other materials: a planning assumption.

°F

60°F uses 1.217×10⁻⁵ ft²/s, the friction-page constant. Other temperatures are interpolated from Engineering Toolbox.

ft

Set to 0 to skip head loss.

Informational. Fixture-unit supply sizing is the plumbing code (IPC or UPC). This page does not size gas, steam, or fire sprinkler pipe.

Velocity

4.085 ft/s

Flow
10 GPM
Reynolds
27,971 · turbulent
Head loss
6.99 ft / 100 ft
Next size
—

Inside diameter, not the nominal size. Not a code size.

Formula

Velocity is 0.408484 times gallons per minute, divided by the inside diameter squared. Flow is velocity times that diameter squared, divided by 0.408484. The minimum inside diameter for a velocity limit is the square root of 0.408484 times the flow, divided by the limit. The friction-loss page uses 0.4085 in its velocity helper. At 10 gallons per minute in a 1 inch bore both print 4.085 feet per second.

v = 0.408484 × Q / d²
Re = v × D / ν
hf = 0.2083 × (100/C)^1.852 × Q^1.852 / d^4.8655

Reynolds number uses the diameter in feet and kinematic viscosity in square feet per second. Below 2,300 is laminar, above 4,000 is turbulent, and the band between is transitional. At 60°F this page uses 1.217×10⁻⁵ ft²/s, the constant already on the friction page. Engineering Toolbox’s 60°F row is 1.2075×10⁻⁵. Other temperatures are a straight interpolation of that Toolbox table. Hazen–Williams head loss is the friction-page function, for water at ordinary temperatures. Feet of head times 0.433 is psi. When the regime is laminar, that head-loss figure is labelled as the formula only, not a design loss. Darcy–Weisbach is the friction page.

The Copper Tube Handbook says a designer should not exceed 8 feet per second in cold water or 5 feet per second in hot water up to about 140°F, and 2 to 3 feet per second when the water is routinely hotter, because of noise and erosion-corrosion. It says the velocity table is for copper tube only. A high velocity here is tagged, and the next listed size that meets the limit is named. That is not an IPC or UPC fixture-unit size, and it is not a gas, steam, or sprinkler size.

Worked examples

10 GPM in a 1.000 in bore. 4.085 ft/s. The same flow in 3/4 inch Type L copper, inside diameter 0.785 in, is 6.629 ft/s. At 60°F the Reynolds number is about 27,971, turbulent. At C = 150 the loss is 6.99 ft per 100 ft, 3.03 psi per 100 ft.

2 inch Schedule 40 at 5 ft/s. Inside diameter 2.067 in, flow 52.30 GPM. 15 GPM at a 5 ft/s limit. Minimum inside diameter 1.107 in. One inch Type L, 1.025 in inside, runs at 5.832 ft/s, over the limit. One and a quarter inch Type L, 1.265 in inside, runs at 3.829 ft/s. That bore at 15 GPM and C = 150 loses 4.72 ft per 100 ft.

Reference

Listed bores are the same tables as the pipe-volume and friction pages: ASME B36.10 Schedule 40 and 80 for steel, ASTM B88 for copper, ASTM F876 SDR-9 for PEX. PVC and CPVC Schedule 40 and 80 in iron-pipe sizes use those same Schedule 40 and 80 dimensions on this site. The stamp on the tube wins.

Questions

How do I calculate water velocity in a pipe?

Velocity in feet per second is 0.408484 times the gallons per minute, divided by the inside diameter in inches, squared. Ten gallons per minute in a 1.000 inch bore is 4.085 feet per second. Nominal size is not the bore.

What is a good velocity for water pipes?

The Copper Tube Handbook says not to exceed 8 feet per second for cold water, or 5 feet per second for hot water up to about 140°F, in copper tube, to limit noise and erosion. Above about 140°F it says 2 to 3 feet per second. That limit is for copper. Other materials are a number you type. This is not a code sizing rule.

How many GPM can a 1 inch pipe carry?

It depends on the inside diameter and the velocity you allow. A 1.000 inch bore at 8 feet per second carries about 19.6 gallons per minute. A 1 inch Type L copper tube is 1.025 inch inside, not 1 inch. The flow-rate page is the bucket test. This page is the pipe.

What size pipe for 10 GPM?

At 8 feet per second the minimum inside diameter is about 0.71 inch. At 5 feet per second it is about 0.90 inch. Then pick the smallest listed tube whose inside diameter is at least that. Fixture-unit sizing in the plumbing code is a different method.

How do I convert GPM to feet per second?

Divide 0.408484 times the GPM by the inside diameter squared. The reverse is velocity times diameter squared, divided by 0.408484.

What is Reynolds number?

Velocity times diameter, divided by kinematic viscosity. Below 2,300 the flow is laminar. Above 4,000 it is turbulent. Between those it is transitional. Ten gallons per minute in a 1 inch bore at 60°F is about 27,970, turbulent.

How much pressure is lost in a pipe?

Hazen–Williams, the same function as the friction-loss page. Ten gallons per minute in a 1.000 inch bore at C = 150 is 6.99 feet per 100 feet, about 3.03 psi per 100 feet. It is for water at ordinary temperatures, and it is not the right tool once the flow is laminar.

Sources

  • Copper Development Association, Copper Tube Handbook, pressure-system sizing. Do not exceed 8 ft/s cold, 5 ft/s hot up to about 140°F, or 2–3 ft/s when the water is routinely hotter. The handbook says the velocity guidance is for copper tube.
  • Hazen–Williams and the pipe inside diameters are the functions and tables already on the friction-loss page. Feet of water times 0.433 is psi. ASME B36.10 and ASTM B88 are the dimension sources named there.
  • The Engineering ToolBox, water kinematic viscosity table. The 60°F row is 1.2075×10⁻⁵ ft²/s. This page’s 60°F Reynolds number uses 1.217×10⁻⁵, the friction-page constant. Other temperatures are interpolated from the Toolbox table.