Formula
Peak-hour demand is each use in the busiest hour times the gallons of hot water for that use. The starting gallons are the worksheet on the U.S. Department of Energy Energy Saver page “Sizing a New Water Heater,” as captured on 1 January 2024. The live address returned 404 on 17 November 2026. Shower 20, shaving 2, hand dishwashing or food prep 3, automatic dishwasher 7, top-loader clothes washer 25, H-axis clothes washer 15. That page says the estimates are averages from information published on websites, and that the worksheet is not total daily use. Its printed example is 3 showers, 1 shave, and 1 hand dishwashing, and it states 66 gallons. The row values are 20, 2, and 3, which add to 65. This page adds the rows.
peak = Σ (uses × gallons)
GPH = BTU/h × efficiency / (8.34 × ΔT)
BTU/h = watts × 3.412
estimate = 0.7 × tank + GPH
Energy Saver says to look for a first hour rating that at least matches the peak hour demand. The example asks for that many gallons or more. The rating is on the EnergyGuide label as Capacity (first hour rating) for a conventional storage heater. The Federal Trade Commission requirement described there does not cover every heat pump model, so the product literature is the place to read a heat pump's rating. Heat-pump-only recovery is slower than resistance heat. Defer to that tested rating.
The 0.76 gas efficiency and the 0.98 electric-resistance efficiency are typical assumptions, not a nameplate. The 0.7 tank fraction is a rule of thumb. It is not the uniform test in 10 CFR 430 Subpart B Appendix E, which is the procedure behind the tested first hour rating. Winter inlet water is colder, so a summer inlet overstates recovery. Staggering showers lowers the peak hour.
Energy Saver says that for most uses you want water heated to 120 °F, and to be cautious of 140 °F because it increases the possibility of scalding. A Building America measure guideline on heat pump water heaters says a mixing valve should be installed when the heater stores water hotter than the tap, and it points at temperatures above about 125 to 130 °F. A setpoint above 140 °F raises a scald note here. Gas venting, the temperature-and-pressure relief valve, and electrical installation belong to a licensed plumber or electrician and the local code. This page does not size a gas pipe and does not calculate combustion or venting.
Worked examples
Gas recovery. 40,000 BTU/h, efficiency 0.76, 50 °F in to 140 °F. 30,400 / 750.6 = 40.5 gallons per hour. Electric. 4,500 W, efficiency 0.98, the same 90 °F rise. 20.0 gallons per hour. Rough first hour. A 40 gallon gas tank on that recovery is 28 + 40.5 = 68.5 gallons. A 50 gallon electric tank is 35 + 20.0 = 55.0 gallons. Both are estimates. Read the EnergyGuide label.
Peak hour with the Energy Saver gallons. 3 showers, 1 dishwasher, 1 top-loader, and 1 hand-dishwashing or food-prep use: 60 + 7 + 25 + 3 = 95 gallons. The same hour with an H-axis washer is 85 gallons. The page's own printed example, 3 showers, 1 shave, and 1 hand dishwashing, adds to 65 gallons from the rows.
Reference
| Use | Gallons |
|---|---|
| Shower | 20 |
| Shaving | 2 |
| Hand dishwashing or food prep | 3 |
| Automatic dishwasher | 7 |
| Clothes washer, top-loader | 25 |
| Clothes washer, H-axis | 15 |
The worksheet does not list a separate bath, shampoo, or hands-and-face row. Hand dishwashing and food prep share one 3 gallon figure.
Questions
What size water heater do I need for a family of 4?
This page does not size by headcount. Add the uses in the busiest hour with the Energy Saver gallons per use. Look for a first hour rating that at least matches that total. The EnergyGuide label prints the tested rating.
What is first hour rating?
It is the gallons of hot water the heater can supply in one hour, starting full. Energy Saver says the EnergyGuide label lists it at the top left as Capacity (first hour rating) on a conventional storage heater. Heat pump models are not all required to carry that label, so use the product literature.
How long does a water heater take to recover?
Recovery in gallons per hour is input times efficiency, divided by 8.34 times the temperature rise. A 40,000 BTU/h gas heater at 0.76 efficiency and a 90 °F rise is about 40.5 gallons per hour. Those efficiencies are typical assumptions you can edit.
Is a 40 or 50 gallon water heater better?
Tank gallons are not the sizing number. A rough estimate of stored hot water is 0.7 times the tank, plus one hour of recovery. That is approximate. The tested first hour rating on the EnergyGuide label is the number to compare with the peak hour.
Does a bigger water heater cost more to run?
A larger tank can lose more heat while it sits. This page does not compute that bill. The kilowatt-hour calculator is for a wattage and a rate you already have.
What temperature should a water heater be set to?
Energy Saver says that for most uses you want water heated to 120 °F, and to be cautious of 140 °F because it increases the possibility of scalding. A tank hotter than the tap needs a mixing valve. This is an estimate, not an installation procedure.
Tank or tankless?
A storage heater is sized by the first hour rating. A tankless heater is sized by simultaneous flow and temperature rise. That calculation is the tankless page. This page does not size a gas pipe.
Sources
- U.S. Department of Energy, Energy Saver, “Sizing a New Water Heater,” captured 1 January 2024 at energy.gov/energysaver/sizing-new-water-heater. The live page returned 404 on 17 November 2026. Peak-hour gallons per use, the first-hour-rating instruction, 120 °F for most uses, and the caution about 140 °F scalding.
- U.S. Department of Energy, Building America Measure Guideline: Heat Pump Water Heaters in New and Existing Homes. A mixing valve when stored water is hotter than the tap.
- 10 CFR 430 Subpart B Appendix E is the name of the uniform test procedure behind a tested first hour rating. The 0.7 tank fraction is not that test.