Formula
Apparent power is the square root of 3 times line-to-line voltage times line current, divided by 1,000. Real power is apparent power times the power factor. Reactive power is apparent power times the sine of the angle whose cosine is the power factor. Line current from kilowatts divides the watts by the square root of 3, the voltage, and the power factor. A motor's input kilowatts are horsepower times 0.746, divided by efficiency, and the current then uses that input and the power factor.
kVA = √3 × V × I / 1000
kW = kVA × PF
I = HP × 746 / (√3 × V × PF × η)
On a wye system, line-to-neutral voltage is line-to-line voltage divided by the square root of 3, and the phase current equals the line current. A delta has no neutral in the basic connection, and the line current is the square root of 3 times the phase current. This page assumes a balanced load. Eaton's 2017 Bussmann handbook writes the three-phase full-load formula with the same square root of 3. The power triangle kVA² = kW² + kVAR² is the identity already on the power-factor calculator. A lower power factor draws more current for the same kilowatts, which is why a utility may bill for reactive power. That current is still not a conductor size. Motor conductor and breaker sizes use NEC 2023 Table 430.250 under 430.6(A)(1). The table numbers were not copied here.
Worked examples
480 V, 100 A, power factor 0.85. 83.14 kVA, 70.67 kW, 43.80 kVAR. Power factor 1. kW equals kVA at 83.14, and kVAR is 0. 50 kW, 208 V, power factor 0.90. 154.2 A. 208 V, 30 A. 10.81 kVA. 208 V line-to-line is 120.1 V line-to-neutral. 480 V is 277.1 V line-to-neutral.
10 HP, 460 V, power factor 0.85, efficiency 0.90. Calculated line current 12.24 A. Conductors and overcurrent protection use NEC 2023 Table 430.250 under 430.6(A)(1), not this number. The table was not copied.
Reference
| Line-to-line | Line-to-neutral | Where it shows up |
|---|---|---|
| 208 V | 120.1 V | 208Y/120 commercial |
| 480 V | 277.1 V | 480Y/277 industrial |
| 400 V | 230.9 V | International |
| 415 V | 239.6 V | International |
| 600 V | 346.4 V | Canada |
NEC 2023 430.6(A)(1) points conductor and branch-circuit protection for a motor at Table 430.250 full-load current, not at a calculated current and not at the nameplate. The table values were not read into this page. Verify with the AHJ or a licensed electrician. These results do not size conductors or breakers.
Questions
How do you calculate 3-phase power?
Apparent power in kVA is the square root of 3, times line-to-line volts, times line amps, divided by 1,000. Real power is that kVA times the power factor. At 480 V and 100 A with a power factor of 0.85, that is 83.14 kVA and 70.67 kW.
How many amps is a 3-phase kilowatt?
Divide the watts by the square root of 3, the line-to-line voltage, and the power factor. 50 kW at 208 V and a power factor of 0.90 is 154.2 A. That current is not a wire size.
Why is there a 1.732 in 3-phase formulas?
1.732 is the square root of 3. Eaton's 2017 Bussmann handbook writes three-phase full-load amps as kVA times 1,000 divided by line-to-line voltage times the square root of 3. The same factor turns line current into apparent power.
What is the difference between kW and kVA?
kW is real power. kVA is apparent power. They match at a power factor of 1. Otherwise kVA is larger, and the difference is reactive power in kVAR. The power-factor page is the longer version of that triangle.
How do I convert kVA to amps for 3-phase?
Amps are kVA times 1,000, divided by the square root of 3 times the line-to-line voltage. 208 V at 30 A is 10.81 kVA, and the reverse uses the same identity.
How many amps does a 10 HP 3-phase motor draw?
At 460 V, a power factor of 0.85, and 90 percent efficiency, the calculated line current is 12.24 A. Conductor and overcurrent sizing use NEC 2023 Table 430.250 full-load current under 430.6(A)(1), not this calculated value and not the nameplate. The table was not copied here.
Is 208 V 3-phase the same as 240 V?
No. 208 V line-to-line is 120.1 V line-to-neutral on a wye. 240 V single-phase is a different system. The same kilowatts at 240 V single-phase draw more current than at 208 V three-phase.
Sources
- Eaton, Bussmann series Selecting Protective Devices handbook no. 3002, 2017. Three-phase full-load amps are kVA times 1,000 divided by line-to-line voltage times the square root of 3.
- The power triangle on this site's power-factor page: power factor is kW divided by kVA, and kVA squared equals kW squared plus kVAR squared.