Available Fault Current Calculator

Transformer secondary fault current and a point-to-point estimate downstream. Infinite bus. Verify with the AHJ or a licensed electrician or engineer.

Checked 2026-11-16. The answer below is computed on this page.

Fault current

Informational estimate. Infinite bus. Motor contribution is not added. Verify with the AHJ or a licensed electrician or engineer.

kVA
V
%

Blank uses Table 4.1.7.6.a, 600 V, three single conductors. A typed C replaces the table and is not a table value.

ft
ft

Uses the first fault current as its start. Zero skips it.

kA

Interrupting rating or SCCR you type. Blank skips the comparison.

At the transformer

23,243 A

FLA
1,202.8 A
C value
Table, until you type one
Downstream
—
Second point
—
Rating
Enter a kA rating
UtilityTransformerFeederPanel

Infinite primary. NEC 2023 110.9, 110.10, and 110.24 are the sections this comparison is aimed at. The code text is not reproduced here.

Formula

Three-phase full-load amps are kVA times 1,000, divided by line-to-line voltage times the square root of 3. Single-phase full-load amps divide by the line-to-line voltage only. The multiplier is 100 divided by the percent impedance. With the high-end tolerance on, the nameplate percent is multiplied by 0.9 first, which is the Bussmann note for 25 kVA and larger UL 1561 transformers. Short-circuit current is full-load amps times that multiplier. On a center-tapped single-phase secondary, the handbook says line-to-neutral current at the terminals is about 1.5 times the line-to-line value, an approximation that can range from 1.33 to 1.67.

f = √3 × L × I / (C × n × E) for three-phase
f = 2 × L × I / (C × n × E) for single-phase
M = 1 / (1 + f)

C comes from Table 4.1.7.6.a in Eaton's Bussmann series Selecting Protective Devices handbook no. 3002, the 2017 edition based on the 2017 NEC. This page uses the 600 V columns for three single conductors in steel or non-magnetic conduit. A size that is not in that table has no C until you type one. A typed C is labelled custom and is not a table value. Length zero returns the starting current. A second length uses the first result as its start. The primary is an infinite bus. Motor contribution is mentioned in the handbook and is not added here.

Worked examples

1,000 kVA, 480 V, three-phase, 5.75 percent, tolerance off. Full-load current 1,202.8 A. Multiplier 17.39. Available current 20,918 A. Tolerance on. About 23,243 A. Custom C of 20,000, which is not a table value, 50 feet, one set. The unrounded transformer current prints as 20,918 A. Downstream, f prints as 0.1887, M as 0.8412, and the current as 17,598 A. Doubling the length and the sets cancels. Against a 10 kA rating the current is over the number you typed. Against 22 kA it is under that number. Either way, verify with the AHJ.

75 kVA, 240 V, single-phase, 2 percent, tolerance off. Full-load current 312.5 A. Line-to-line 15,625 A. Line-to-neutral at the terminals about 23,438 A. Then 25 feet, one set, custom C 15,000, line-to-line: f 0.217, M 0.8217, about 12,839 A.

Reference

Available fault current is the current the source can deliver into a bolted fault. Breaker interrupting ratings and equipment short-circuit current ratings are compared with it. NEC 2023 110.9, 110.10, and 110.24 are the sections that comparison is aimed at. The code text is not copied here. A change in the service can require the field marking to be updated. Verify with the AHJ or a licensed electrician or engineer.

An arc-flash study under NFPA 70E needs an engineer.

Questions

How do you calculate available fault current?

At the transformer, full-load amps times 100 divided by the percent impedance. A 1,000 kVA, 480 V, three-phase transformer at 5.75 percent impedance is about 20,918 A on an infinite bus. Downstream, the point-to-point factor reduces that current.

What is the point-to-point method?

Eaton's 2017 Bussmann SPD handbook, section 4.1.5, walks the fault from one point to the next. The f factor uses length, the starting current, the C value, the number of conductors per phase, and the voltage. M is 1 divided by 1 plus f.

How does transformer impedance affect fault current?

A lower percent impedance lets more current through. The handbook says 25 kVA and larger UL 1561 transformers have a ±10 percent tolerance, and the high end multiplies the nameplate percent by 0.9.

What does NEC 110.24 require?

It is the section aimed at marking the available fault current and the date at non-dwelling service equipment, and at re-marking after a change. The code text is not reproduced here. The AHJ decides what gets marked.

What is the difference between AIC and SCCR?

An interrupting rating is what an overcurrent device can interrupt. An SCCR is the short-circuit current rating of other equipment. This page compares the calculated current with the kA number you type. It does not assign either rating.

Why is fault current higher at the transformer?

The conductors have not yet added impedance. Length, a smaller conductor, and fewer parallel sets all raise the f factor and lower the current at the next point.

Does fault current go up with a bigger transformer?

On an infinite bus, full-load amps rise with kVA, so the secondary fault current rises if the percent impedance stays the same. The nameplate impedance still controls the multiplier.

Sources

  • Eaton, Bussmann series Selecting Protective Devices handbook no. 3002, 2017 edition, based on the 2017 NEC. Section 4.1.5 point-to-point method, including the full-load formulas, the 0.9 multiplier on percent impedance, the 1.5 line-to-neutral approximation, and Table 4.1.7.6.a C values for 600 V three single conductors. C is one over the impedance per foot, from the IEEE Gray Book and Buff Book values named in that table note.