Formula
The optional method, NEC 2023 220.82, applies to a dwelling served by one 120/240 V or 208Y/120 V, three-wire set of service or feeder conductors of 100 A or more. General load is 3 VA per square foot, plus 1,500 VA for each small-appliance circuit and each laundry circuit, plus the nameplate of fastened, permanently connected, or dedicated appliances. The first 10 kVA of that total is at 100 percent and the remainder is at 40 percent. Heating and air conditioning are added afterward, and only the largest 220.82(C) selection. Heat is not inside the general load.
general = 100% of the first 10 kVA + 40% of the rest
amps = total VA ÷ 240
The standard method keeps the lines apart. Lighting is 220.41 at 3 VA per square foot. Small-appliance and laundry circuits are 220.52 at 1,500 VA, and they join the lighting total before Table 220.45. That table, in the 2023 reorganization, is the old lighting demand table: first 3,000 VA at 100 percent, from 3,001 VA through 120,000 VA at 35 percent, and the remainder at 25 percent. A first-revision draft numbered the same table 220.452. The published summaries of the 2023 code call it Table 220.45. Fastened appliances other than the range, dryer, heat, and air conditioning are 220.53: 100 percent, or 75 percent when four or more are each 500 W or 1/4 hp or more. The dryer is 220.54, 5,000 VA or the nameplate, whichever is larger. The range is Table 220.55 Column C, 8 kW through 12 kW, plus Note 1 above 12 kW. Heat and air conditioning use 220.60, the larger of the two. The largest motor adds 25 percent under 220.50. NEC 220.83, for an existing dwelling, is a further option and is not calculated. The 100 A floor is 230.79(C) for a one-family dwelling.
Worked examples
2,000 ft², two small-appliance circuits, one laundry, 12 kW range, 5 kW dryer, 4,500 VA water heater, 1,200 VA dishwasher, 900 VA disposal, gas heat, 7,200 VA air conditioning. Optional method: general load 34,100 VA becomes 19,640 VA, plus 7,200 VA, total 26,840 VA, 111.8 A, 125 A service. With 15 kW of central electric heat, the heat at 65 percent is 9,750 VA and replaces the air conditioning. Total 29,390 VA, 122.5 A, still a 125 A service.
The same house, standard method, no motor adder. Lighting demand 5,625 VA, fastened appliances 6,600 VA, dryer 5,000 VA, range 8,000 VA, air conditioning 7,200 VA. Total 32,425 VA, 135.1 A, 150 A service. Adding a 1,000 VA fastened microwave makes four appliances at 75 percent, 5,700 VA. A 14 kW range is 8,800 VA. A 4,000 VA dryer nameplate is still 5,000 VA.
Reference
The result is an estimate of service size, not the sum of the breaker handles. Adding an EV charger means typing its nameplate into the other fastened load and calculating again. A 2023 summary of 220.5(C) counts garage floor area. The 220.82(B) first-revision text still named garages among the areas left out. Type the area the authority having jurisdiction counts.
Questions
What size electrical panel do I need for a 2,000 sq ft house?
The optional method for the base house on this page, with a 12 kW range, a 5 kW dryer, a 4,500 VA water heater, a dishwasher, a disposal, and 7,200 VA of air conditioning, is 26,840 VA, 111.8 A, and a 125 A service. The standard method for the same house is 32,425 VA, 135.1 A, and a 150 A service. Both are estimates.
Is 100 amp service enough?
NEC 230.79(C) sets a one-family dwelling service disconnect at not less than 100 A. A calculated load under 100 A still shows 100 A here. Whether that service can take another appliance is a new calculation, not a guess from the main breaker.
Can I add an EV charger to a 200 A panel?
Add the charger nameplate to the fastened-appliance line and run the estimate again. On the optional method it joins the general load before the 10 kVA / 40 percent step. This page does not say a 200 A panel has room. The official calculation is the electrician's or the AHJ's.
What is the difference between the optional and standard method?
NEC 2023 220.82 is the optional method for a dwelling with a 100 A or larger service: first 10 kVA at 100 percent, the rest of the general load at 40 percent, then the largest heating or cooling selection. The standard method, Part III, keeps lighting, appliances, the dryer, the range, and heat versus air conditioning on separate lines. It is usually the larger number.
Does a load calculation include the air conditioner and the heat?
Not both at once. Optional method 220.82(C) takes the largest of the listed heating and cooling selections. Standard method 220.60 takes the larger of the heating and cooling nameplates.
How many amps does a house use?
Divide the calculated volt-amperes by 240. That is a demand estimate, not the sum of the breaker handles and not a measurement of what the house draws tonight.
Do I need a permit to upgrade the service?
A service change typically needs a permit. The authority having jurisdiction decides. This estimate is not that permit calculation.
Sources
- NFPA 70 first-revision text for the 2023 cycle: 220.82(A) through (C), including the six heating and cooling selections; 220.53; 220.54; Table 220.55 Note 1; 220.60; and the lighting demand steps of first 3,000 VA, then through 120,000 VA at 35 percent, remainder at 25 percent. That draft table was numbered 220.452.
- Published 2023 summaries: dwelling minimum unit load is 220.41 at 3 VA per square foot, and the lighting demand factors are Table 220.45. Small-appliance and laundry circuits remain 220.52 at 1,500 VA.
- NEC 230.79(C), the one-family dwelling service disconnect minimum of 100 A, used here as that floor. The section text was not reprinted.