Heat Pump Size Calculator

Heat pump tons, balance point, and backup heat from design loads and rated capacity. An estimate, not Manual J. Not refrigerant line or circuit sizing.

Checked 2026-11-09. The answer below is computed on this page.

Loads and ratings

BTU/h
BTU/h
°F

Use the ASHRAE 99% heating design temperature for the location. ASHRAE Handbook — Fundamentals, climatic design information, is where that table lives.

°F

Assumption: the outdoor temperature where the house needs no heat. 65 °F is the default, not a measured balance.

BTU/h
BTU/h
BTU/h

Optional. From the NEEP cold-climate list or the manufacturer’s extended data. Blank means the 47/17 line is extrapolated.

Optional. Fills cooling capacity as tons × 12,000.

BTU/h
% of load

Default 100 to 115 percent is the air-conditioner limit in the 2009 ICC summary of ACCA Manual S. That same table sizes heat pumps at 115 or 125 percent of cooling load by climate. Editable. Not a Manual S selection.

% of load

An estimate, not Manual J. Have a licensed HVAC contractor perform a load calculation and confirm equipment selection, refrigerant work and electrical supply to local code. No refrigerant line or strip-heat circuit is sized here.

Balance point

25.82 °F

At design
16,400 BTU/h
Auxiliary
23,600 BTU/h · 6.92 kW
Cooling
2.5 tons · 120%
Fit
oversized
Heating load and heat-pump capacity against outdoor temperature, with the balance point marked where the lines meet. BTU/h Outdoor °F Balance 25.8 °F 5° 65° Solid line is the house load. Lighter line is heat-pump capacity. An estimate, not Manual J.

Estimate only, not a Manual J load calculation or Manual S equipment selection.

An estimate, not Manual J. Capacity falls as it gets colder. The balance point is where the two lines meet.

Formula

The house load is a straight line from the design heating load at the winter design temperature to zero at the base temperature. Capacity is a straight line between the 47 °F and 17 °F ratings. Below 17 °F, a 5 °F rating makes the next segment. Without it, the 47/17 line keeps going and the result says it is extrapolated. An estimate, not Manual J.

L(T) = Ldesign × (Tbase − T) / (Tbase − Tdesign)
C(T) = C17 + (C47 − C17) × (T − 17) / 30
aux = max(0, Ldesign − C(Tdesign))
kW = BTU/h ÷ 3,412.14

The balance point is the temperature where those two lines are equal. Auxiliary heat is the gap at the design temperature, never a negative. Tons are the cooling load divided by 12,000. A selected unit’s percent of the cooling load is tagged against the band you set. The default band is 100 to 115 percent, the air-conditioner window in Wes Davis’s January–February 2009 ICC Building Safety Journal summary of ACCA Manual S. That article’s heat-pump row is 115 or 125 percent of the cooling load, depending on climate, not a copy of the air-conditioner row. The band is editable and this is not a Manual S selection.

NEEP’s cold-climate specification asks for capacity at 47 °F, 17 °F, and 5 °F, and it says the rated column should match the AHRI certificate at 47 °F and 17 °F. NEEP’s cold-climate sizing guide says to use extended performance data at the local design temperature, and it discusses sizing to the heating load or leaving a balance point where auxiliary heat starts. Oversizing the cooling capacity is what the Manual S cooling limit is trying to avoid: short cycles and weak dehumidification. The CEE decision guide on the Department of Energy’s building-science site says Manual S tends to size for cooling and then add supplemental heat, and that a heating-dominated house sized as the only heat source should be checked against the heating design load. Buy from a Manual J and a contractor.

Worked examples

Cold climate. 40,000 BTU/h at 5 °F, base 65 °F, 36,000 at 47 °F, 22,000 at 17 °F, no 5 °F number. Balance point 25.82 °F. Capacity at 5 °F is 16,400 BTU/h, 41% of the load, extrapolated. Auxiliary heat is 23,600 BTU/h, 6.92 kW.

Milder. 30,000 BTU/h at 15 °F, 30,000 at 47 °F, 24,000 at 17 °F. Balance point 23.0 °F. Capacity at 15 °F is 23,600. Auxiliary heat is 6,400 BTU/h, 1.88 kW. With a 5 °F rating of 18,000 on the first house, capacity at design is 18,000, auxiliary heat is 22,000 BTU/h, 6.45 kW, and the balance point stays 25.82 °F because it sits on the 47/17 segment.

Cooling. 30,000 BTU/h is 2.5 tons. A 36,000 BTU/h unit is 120%, oversized on a 100–115% band. A 30,000 BTU/h unit is 100% and fits. No auxiliary heat. 20,000 BTU/h at 17 °F, 24,000 at 17 °F and 34,000 at 47 °F: auxiliary heat is 0, and the balance point is 11.67 °F, below design, on the extrapolated segment.

Reference

The chart runs from the design temperature to the base temperature. The solid line is the house. The dashed line is capacity. Electric auxiliary heat comes in kilowatt steps the manufacturer lists. This page only converts the BTU gap.

Questions

What size heat pump do I need?

The cooling load and the heating load, not the square footage. Cooling tons are the cooling load divided by 12,000. Heating is whether the capacity at the winter design temperature covers that load, and how much auxiliary heat is left. This page is an estimate, not Manual J.

How many tons for my house?

Cooling load divided by 12,000. A 30,000 BTU/h cooling load is 2.5 tons. A 36,000 BTU/h unit is 120% of that load. There is no square-foot factor on this page.

What is a heat pump balance point?

The outdoor temperature where the house load line crosses the heat pump’s capacity line. Below it, the load is larger than the capacity and auxiliary heat has to make up the difference. The U.S. Department of Energy’s building-science notes describe that crossing, and a capacity balance point as the temperature where the heat pump no longer covers the load.

Do I need backup heat?

When capacity at the design temperature is below the heating load, yes, for that gap. The kilowatts are the BTU gap divided by 3,412.14. Electric strip heat still comes in element steps this page does not list. A dual-fuel furnace is the other backup. This page does not size the circuit.

Can a heat pump heat my house at 0 °F?

Only if its capacity at that temperature covers the load. Below 17 °F this page uses a 5 °F rating when you enter one. Without it, the 47/17 line is extrapolated and labelled that way. Check the manufacturer’s low-temperature data or the NEEP cold-climate list.

How do I read capacity at 17 °F and 5 °F?

The 47 °F and 17 °F numbers are the AHRI rating points NEEP tells manufacturers to report in the rated column. The NEEP cold-climate specification also asks for capacity at 5 °F. Type the maximum heating capacity from the certificate or that list, not a nominal tonnage.

Do I need a Manual J?

Yes, before you buy. This page is an estimate, not Manual J. Have a licensed contractor run the load and confirm the equipment, the refrigerant work, and the electrical supply.

Sources

  • U.S. Department of Energy, Building Science Education, “Heat Pumps” (Renewable Energy Systems, chapter 11). The balance point is where the heating-demand line crosses the heat pump’s maximum capacity. Below it, supplemental heat covers the gap. Capacity in that figure comes from extended performance data or the NEEP database.
  • NEEP, Cold Climate Air-Source Heat Pump Specification, version 2.0. Reporting table at 47 °F, 17 °F, and 5 °F. The rated column is the AHRI certificate capacity at 47 °F and 17 °F.
  • NEEP, “Guide to Sizing and Selecting Air-Source Heat Pumps in Cold Climates.” Use extended performance data at the local design temperature. One path is capacity at design between 100 and 115 percent of the heating load. Another is auxiliary heat with a balance point around 20 °F or below.
  • Consortium for Energy Efficiency, via the Department of Energy building-science library, “ASHP Decision Matrix and System Design Guide.” Manual J for the load. Manual S for selection. In heating-dominated climates, size a sole-source heat pump to the heating design load and then check dehumidification.
  • Wes Davis, “Reviewing HVAC Designs for Compliance with ACCA Manual S,” ICC Building Safety Journal, January–February 2009, Table 1. Air conditioners: 100–115 percent of total cooling load in the article’s example. Heat pumps: 115 or 125 percent of the cooling load. This page is not that selection.