Battery Runtime Calculator

Battery life calculator with inverter efficiency, depth of discharge, and Peukert’s exponent for lead-acid.

Checked 2026-10-17. The answer below is computed on this page.

Battery and load

Amp-hours, volts, and watts do not change between imperial and metric.

Ah
V
W
%
%

1 skips the extra reduction. About 1.05 is sometimes quoted for LiFePO4. k = 1 is used here so the effect stays negligible.

h

20 hours is the usual C20 rating the exponent was fit to.

Peukert runtime

2.67 h

Energy limit, k = 1
4.25 h
Battery current
11.76 A

Depth of discharge and the exponent are typical practice, not a standard. The battery still ages with each cycle. Off-grid solar calculator sizes the bank. This page times the one you have.

Formula

Current is taken from the battery, after the inverter. Usable capacity is the rated amp-hours times the depth of discharge. The energy limit is that capacity divided by the current, which is the same as the Peukert expression with the exponent set to 1. The lead-acid line raises the exponent.

I = watts ÷ (volts × inverter efficiency)
t = H × ((C × DoD) / (I × H))^k

H is the rating period, 20 hours unless you change it. A lithium pack with k = 1 does not get a second reduction. Some LiFePO4 data sheets sit near 1.05. At 1.05 the change is small, and this page’s lithium preset keeps k at 1 so you can see the energy limit on its own. Flooded lead-acid is started at 50% discharge and k = 1.3. AGM at 50% and k = 1.1. Those are manufacturer-practice figures, not a standard. If the watts came from a voltage and a current, that product is the Ohm’s law calculator.

Worked examples

100 Ah, 12 V, 120 W, 85% inverter, 50% discharge, k = 1.3, 20-hour rating. Battery current is 11.76 A. The energy limit is 4.25 hours. Peukert brings it to 2.67 hours.

The same battery with k = 1. Runtime stays at 4.25 hours. That is the lithium preset’s exponent, though the lithium preset also raises the discharge limit to 80%, which lengthens the run.

Reference

The two hours are always both on the readout. Use the Peukert line for flooded and AGM. Use the energy line when k is 1.

Questions

How long does a 100 Ah, 12 V battery run a 120 W load?

At 85% inverter efficiency the battery supplies 11.8 A. Using half the capacity, the energy limit is 4.25 hours. With a lead-acid Peukert exponent of 1.3 that falls to about 2.67 hours. A lithium exponent of 1 stays at 4.25 hours.

What is Peukert’s exponent?

A lead-acid battery delivers fewer of its rated amp-hours as the current rises. The usual form against the 20-hour rating is t = 20 × ((usable Ah) / (amps × 20))^k. k near 1.3 is a flooded starting point. k = 1 means the effect is ignored, which is the right default for LiFePO4.

Does inverter efficiency change the current?

Yes. The watts are on the AC side. The battery current is watts ÷ (volts × efficiency). An 85% inverter makes the battery work harder than the load’s wattage suggests.

Sources

  • Peukert’s equation in the C20 form t = H ((C · DoD) / (I · H))^k. H defaults to 20 hours.
  • Inverter efficiency is applied to the battery current, not as an after-the-fact fudge on the hours.
  • Flooded k ≈ 1.3 and 50% DoD, AGM k ≈ 1.1 and 50%, LiFePO4 k ≈ 1 and 80% are typical practice. A k near 1.05 is sometimes quoted for LiFePO4. This page’s lithium preset uses 1.