Boiler Size Calculator

An estimate of boiler output from EDR, a known heat loss, or a square-footage sketch. Not Manual J. No gas pipe and no vent.

Checked 2026-11-19. The answer below is computed on this page.

Boiler

An estimate, not a Manual J. No gas pipe, no vent, and no combustion-air calculation. A licensed heating contractor installs it.

sq ft

Default 1.33 is the common steam allowance. Editable.

0.50 to 0.99. An approximation of input, not a DOE heating-capacity test.

Gross output

127,680 BTU/h

Net
96,000 BTU/h
Input
—
Next listed input
—

Estimate, not Manual J. Avoid oversizing, especially a modulating hot-water boiler. No gas pipe and no vent.

Formula

Steam output starts at 240 BTU/h per square foot of EDR. AHRI Standard 1500-2024 gets steam square feet by dividing the rounded steam net rating by 240, and it gets the net rating by dividing gross output by the piping and pickup factor in its Table 1. The 1.33 multiplier here is the common steam allowance, running that definition in reverse: gross is about net times 1.33. It is editable. Cleaver-Brooks lists 150 BTU/h per square foot of hot-water EDR. A lower-temperature correction was not read, so 150 stays fixed unless you type another rate. A cast-iron section chart was not read, so EDR is a number you enter.

steam net = EDR × 240
steam gross = net × pickup
hot water = EDR × 150
input = output ÷ AFUE

Input divided by AFUE is an approximation. A real boiler is rated by DOE heating capacity and by an AHRI net rating. Gross is the tested output. Net is what is left for the radiation after piping and pickup. The square-footage mode uses the room BTU page's planning rates, 25 through 60 BTU/h per square foot for zones 1 through 8. The furnace page does not publish that table. Area times a rate is an estimate, not a Manual J. A known heat loss can include an indirect domestic-hot-water add you type. Outdoor reset and a combi boiler's domestic load are not modelled. No gas pipe, no vent, and no combustion air.

Worked examples

400 sq ft EDR, steam, pickup 1.33. Net 96,000 BTU/h. Gross 127,680 BTU/h. 300 sq ft EDR, hot water, 150. 45,000 BTU/h. 60,000 BTU/h heat loss at 0.95 AFUE. 63,158 BTU/h input.

2,000 sq ft, zone 4, multiplier 1. 40 BTU/h per square foot gives 80,000 BTU/h output. At 0.85 AFUE the input is 94,118 BTU/h. 80,000 BTU/h is 23.45 kW.

Reference

Oversizing a hot-water or modulating boiler short-cycles it. Match the output to the load, then let the contractor apply the rating plate. Installation is a licensed heating contractor's work under the local code.

Questions

What size boiler do I need for my house?

A hot-water boiler follows the design heat loss. A steam boiler follows the connected radiation. Two thousand square feet times 40 BTU/h per square foot is only this site's zone-4 planning rate, 80,000 BTU/h. It is not a Manual J.

How do I calculate EDR for radiators?

This page takes the total square feet of EDR you already have. A cast-iron section chart was not read, so there is no sections-to-EDR table. Steam uses 240 BTU/h per square foot.

How many BTU per square foot for a boiler?

The room BTU page uses 25 through 60 BTU/h per square foot for climate zones 1 through 8. Those are planning midpoints. The furnace page does not publish a climate table. Neither number is a Manual J.

What is the difference between net and gross boiler ratings?

AHRI 1500-2024 divides gross output by a piping and pickup factor to get the net rating, then divides a steam net rating by 240 to get square feet. The 1.33 factor here is the common steam allowance, labelled as such.

Is a bigger boiler better?

Not past the load. Extra capacity short-cycles a boiler, and a modulating hot-water boiler is especially sensitive to that. The result is an estimate.

Boiler vs furnace sizing?

Both want a heat loss for forced air or hot water. Steam is the exception: size it to the connected radiation. The furnace page is the forced-air version of the output check.

What size combi boiler do I need?

Add the space-heating output and the domestic-hot-water load you type. This page does not pick a combi model, and it does not size a gas pipe or a vent.

Sources

  • ANSI/AHRI Standard 1500-2024 (I-P). Net rating is gross output divided by the Table 1 piping and pickup factor. Steam square feet are that net rating divided by 240.
  • Cleaver-Brooks steam calculator notes: 1 sq ft EDR steam = 240 Btu/h, and 1 sq ft EDR hot water = 150 Btu/h.
  • This site's room BTU page: planning rates of 25 through 60 BTU/h per square foot for zones 1 through 8. Not a DOE table and not Manual J.